Page 96 of 456 Installing DC power
Note 2: The Large Candeo system generally requires one input receptacle for each rectifier, within 1.8 m (6 ft) of each rectifier. The commercial power receptacles required are determined by the number and type of rectifiers used.
Note 3: The Small Candeo system requires two 30 A feeds for each rectifier shelf, with each shelf supporting five or six rectifiers.
In a single frame configuration, a Candeo system can power a complete range of
•Large Candeo: Built around the shelfless Candeo Rectifier 50/48, this system operates from any voltage between 80 V AC to 300 V AC (single phase). When configured with 50 A Candeo rectifiers, the system delivers up to 500 A from a single 1.05 m (42 in.) frame and up to 1000 A from a single 2.1 m (84 in.) frame.
•Small Candeo: Built around the Candeo Rectifier 30/48, this system operates from any voltage between 75 V AC to 310 V AC (single phase). When configured with 30 A Candeo rectifiers, the system delivers up to 150 A from a single rectifier shelf and up to 300 A from a system equipped with a supplementary rectifier shelf. The Small Candeo system comes in 1.3 m (51 in.) and 2.1 m (84 in.) versions.
More detailed information is supplied in the following Candeo power system manuals, which are included with the system and also available on the Partner Information Center web page:
•Candeo MP481200 Power System User Manual (P0914425)
•Candeo MP481200Power System Installation Guide (P0914426)
•Candeo SP 48300 Power System User Manual (P7000154)
•Candeo SP 48300 Power System Installation Manual (P7000289)
•Candeo SP 48300 Power System Quick Installation Guide for Meridian 1 and Communication Server 1000 Systems (N0029343)