Page 100 of 456 Installing DC power

Large Candeo sample configurations

Example configuration #1

1.05 m (42 in.) Frame with battery kit, LVD and distribution 500 (with 20 breaker positions).

17 mid trip breakers (30 A), one GMTX fuse block (takes up 3 breaker positions).

System monitor.

Up to 10 rectifiers (500 A capacity).

Example configuration #2

1.05 m (42 in.) Frame with battery kit, LVD and distribution 500 (with 20 breaker positions). 17 mid trip breakers (30 A), one GMTX fuse block (takes up 3 breaker positions).

Additional distribution 500 (with 20 breaker positions). 11 mid trip breakers (30 A), three GMTX fuse blocks (takes up 3 breaker positions per block).

System monitor.

Up to 6 rectifiers (300 A capacity).

Example configuration #3

2.1 m (84 in.) Frame with battery kit, LVD and distribution 500 (with 20 breaker positions). 20 mid trip breakers (30 A).

Second 2.1 m (84 in.) Frame with battery kit, LVD and distribution 500 (with 20 breaker positions). 11 mid trip breakers (30 A), three GMTX fuse blocks (takes up 3 breaker positions per block).

Additional distribution 500 (with 20 breaker positions), 10 mid trip breakers (30 A).

System monitor.

Up to 10 rectifiers (500 A capacity) in frame one, up to 10 rectifiers (500 A capacity) in frame two.

One interframe DC link bar kit.

NN43021-310 Standard 02.01 December 2007