Page 112 of 456 Installing DC power

Note 1: The frame ground collector cable is normally sized according to its length (distance between the main DC distribution cabinet and the FGB or BPG) as well as the maximum fuse or circuit breaker size that can be provided in the power plant. Refer to Table 3 for the recommended cable size for the Candeo power system.

Note 2: The frame ground drop into the Candeo frame must be the same size as the frame ground collector. The frame ground drop into battery stands, racks or stacks is usually #6 AWG.

Table 3

Recommended cable size for the frame ground collector

 

 

 

 

Recommended size

Cable length

 

 

(see notes 1 and 2 above)

 

 

 

 

 

 

0 to 6 m (0 to 20 ft)

 

#2 AWG

 

 

 

 

 

 

 

6 to 12 m (20 to 40 ft)

 

#0 AWG

 

 

 

 

 

 

 

12 to 24 m (40 to 80 ft)

 

#0000 AWG

 

 

 

 

 

 

 

24 to 50 m (80 to 160 ft)

 

#500 kcmil

 

 

 

 

 

 

 

 

Table 4

 

 

 

 

 

Torque values for bolted connections (Part 1 of 2)

 

 

 

 

 

 

 

Bolt size

 

Threads/inch

Torque (in.-lb)

 

Tension (lb)

 

 

 

 

 

 

 

#8

 

32

 

18

 

625

 

 

36

 

20

 

685

 

 

 

 

 

 

 

#10

 

24

 

23

 

705

 

 

32

 

32

 

940

 

 

 

 

 

 

 

6 mm (1/4 in.)

 

20

 

80

 

1840

 

 

28

 

100

 

2200

 

 

 

 

 

 

 

8 mm (5/16 in.)

 

18

 

140

 

2540

 

 

20

 

150

 

2620

 

 

 

 

 

 

 

9.5 mm (3/8 in.)

 

16

 

250

 

3740

 

 

24

 

275

 

3950

 

 

 

 

 

 

 

NN43021-310 Standard 02.01 December 2007

Page 112