Configuring the system monitor Page 153 of 456

Configuring the System Monitor

The master System Monitor (NT8D22) interfaces with a Serial Data Interface (SDI) port in the column with CPU 0.

Procedure 15

Configuring the System Monitor (NT8D22)

1Set the baud rate for the SDI port associated with the system monitor to 1200 baud in DTE mode.

2In the rear of the pedestal, loosen the two retaining screws on the system monitor and remove it from the PDU.

3Configure the option switches for each system monitor. (See Circuit Card: Description and Installation (NN43001-311) for a detailed description of switch setting options.)

a.For a single-column system, configure the switches as shown in Table 7.

Note: Connect and cable the system monitor in a single-column system like a master system monitor for the rest of this procedure.

Table 7

NT8D22 switch settings for a single-column system

Switch

1

2

3

4

5

6

7

8

 

 

 

 

 

 

 

 

 

SW1

off

off

*

on**

off

off

off

off

SW2

on

Always

on

on

on

on

on

on

 

 

off

 

 

 

 

 

 

SW3

on

on

on

on

 

 

 

 

 

 

*

Set to on for a DC-powered system; set to off for an AC-powered system.

**

Set to off if the system is not equipped with a PFTU.

 

 

 

 

 

 

 

 

 

 

 

 

b.For a multiple-column system, configure the system monitor in the column with CPU 0 as the master, using the settings shown in Table 8 and Table 10 on page 154.

c.Configure option switches on slave system monitors as shown in Table 9 on page 154 and Table 11 on page 156. If CPU 0 and CPU 1 are in different columns, configure the system monitor in the column

Communication Server 1000M and Meridian 1 Large System Installation and Commissioning

Page 153
Image 153
Nortel Networks 1000M warranty Procedure Configuring the System Monitor NT8D22