Installation and Test for Multi-Carrier Cabinets 555-230-112

May 1998

 

 

3Install Management Terminal and Activate System

Install Management Terminal

Page 3-2

Install Management Terminal

Locate the management terminal within 50 feet (15.2 m) of the system. It may be necessary to reduce the maximum distance limitation if higher gauge wire is used or if the capacitive load on the line is increased. In general, connect the terminal directly to the system with the shortest possible cable. For maintenance purposes, locate the terminal in the same equipment room as the system or in sight of the system.

NOTE:

The management terminal in Figure 3-1 is shown for illustration purposes only and does not represent a specific terminal type.

Figure 3-1. Typical Management Terminal

The following types of terminals can connect to a system:

715 BCS

2900/715 BCS

715 BCS-2

The following notes apply:

This chapter emphasizes terminal installation in Release 6 and later systems.

If the terminal supports a DC-powered system, install a 116A Isolator (comcode 106005242).

Connect an optional printer using a locally obtained EIA cord. See

Appendix B, ‘OptionSwitch Settings’’ for printer option switch settings.