DEFINITY Enterprise Communications Server Release 6

Issue 5

Installation and Test for Multi-Carrier Cabinets 555-230-112

May 1998

 

 

3Install Management Terminal and Activate System

Set System Maintenance Parameters

Page 3-18

Set System Maintenance Parameters

If the system does not contain a TN778 Packet Control circuit pack, skip this

section and proceed to ‘AdministerSystem Configurations (Release 6r)’.

1.Verify the terminal screen displays: Command:

2.Type change system-parameters maintenance and press Enter. Verify the screen displayed is similar to Screen 3-5. The screen shows default values and the cursor is positioned on Product Identification: line.

Screen 3-5. Typical System-Parameters Maintenance Screen

! CAUTION:

To prevent unnecessary trouble tickets, do not enable the system alarms (Alarm Origination feature) until all installation and administration procedures are completed.

3.Move the cursor by pressing Tab to move down the screen from field to field and enter y in the Packet Bus Activated? field to indicate a TN778 circuit pack is installed. This is the only field needing change on this screen to turn the red LEDs off.

4.Press Enter when the information is correct.

Page 121
Image 121
Lucent Technologies Release 6 Set System Maintenance Parameters, Screen 3-5. Typical System-Parameters Maintenance Screen