DEFINITY Enterprise Communications Server Release 6 | Issue 5 |
Installation and Test for | May 1998 |
1 Install and Connect Cabinets |
|
Connect AC Power and Ground | Page |
|
|
!
CAUTION:
The equipment room AC power and ground wiring must be performed by a qualified electrician. Refer to DEFINITY Enterprise Communications Server Release 6 System Description Pocket Reference, for site requirement information.
!
CAUTION:
The power circuit must be dedicated to the system and must not be shared with other equipment and must not be controlled by a wall switch. The AC receptacle should not be located under the MDF.
!
CAUTION:
System grounding must comply with the general rules for grounding contained in Article 250 of the National Electrical Code (NEC), National Fire Protection Agency (NFPA) 70, or the applicable electric code in the country containing the equipment. For more information, refer to ‘Approved‘
Grounds’’ on page
Connect Ground to AC-Powered System (J58890CE)
Grounding is relatively simple for an
■The approved ground wire must be a green (or green with yellow stripe), 6 AWG (#40) (16 mm2), copper, stranded wire.
■Bond all approved grounds at the
AC Load Center is 50 Feet (15.2 m) or Less from
Cabinet
1.At the bottom rear of the PPN cabinet, connect a 6 AWG (#40) (16 mm2) CABINET GROUND wire to the cabinet ground terminal block. See Figure
2.Route the CABINET GROUND wire to the
3.At the bottom rear of the first EPN cabinet (if provided), connect a 6 AWG (#40) (16 mm2) CABINET GROUND wire to the cabinet ground terminal block.
4.Route the CABINET GROUND wire to the