DEFINITY Enterprise Communications Server Release 6 | Issue 5 |
Installation and Test for | May 1998 |
5 Install and Wire Telephones and Other Equipment |
|
Connect Power Distribution Unit External Alarm Wires | Page |
|
|
1.Choose an alarm to connect (such as Battery Interface Failure).
2.Choose the port circuit pack to use and its carrier and slot number (from Table
3.Choose a port circuit on the port circuit pack, for example Port 3.
4.Install
![]()
NOTE:
It is recommended that the RFA, ACF, and BIF alarm leads be connected to the major alarm device and the BOD alarm leads be connected to the minor alarm device.
5.Connect the major and minor alarm devices to the appropriate cross- connect pins on the MDF.
6.Administer the alarms using DEFINITY Enterprise Communications Server Release 6 Administration and Feature Description.