5 Install and Wire Telephones and Other Equipment

 

Connect Power Distribution Unit External Alarm Wires

Page 5-21

 

 

1.Choose an alarm to connect (such as Battery Interface Failure).

2.Choose the port circuit pack to use and its carrier and slot number (from Table 5-3). For example TN2183 Analog Line, Cabinet 1, Carrier C, Slot 1.

3.Choose a port circuit on the port circuit pack, for example Port 3.

4.Install cross-connect jumpers to connect the named pins from the alarm wires to the appropriate pins on the port circuit pack.

NOTE:

It is recommended that the RFA, ACF, and BIF alarm leads be connected to the major alarm device and the BOD alarm leads be connected to the minor alarm device.

5.Connect the major and minor alarm devices to the appropriate cross- connect pins on the MDF.

6.Administer the alarms using DEFINITY Enterprise Communications Server Release 6 Administration and Feature Description.