Installation and Test for Multi-Carrier Cabinets 555-230-112

May 1998

4 Test the System

 

Test Tone-Clock for each EPN

Page 4-10

 

 

Test Tone-Clock for each EPN

1.Verify the screen displays: Command:

2.Type test tone-clock 2A (where 2A is the cabinet and carrier number for one of the Tone-Clocks installed) and press Enter.

NOTE:

Circuit pack positions are usually given by cabinet, carrier, and slot. They may also be given by port. The term “cabinet” refers to 1 Multi-Carrier Cabinet making up one port network. A port network is defined as a group of cabinets connected together with 1 TDM bus.

If any result is FAIL, check the associated TDM bus cables and intercabinet cables in the EPN.

3.Repeat Step 2 for each installed Tone-Clock circuit pack.

Test Tone-Clock Interchange for each

EPN

Critical reliability only.

1.Verify the screen displays: Command:

2.Type status system all-cabinetsand press Enter. This displays the location of the Standby Tone-Clock.

3.Type set tone-clock xxx (where xxx is the port network/carrier for the standby tone-clock). Press Enter.

4.Type status system all-cabinets and press Enter.

5.Verify the duplicated Tone-Clock is active using the information displayed on the screen.

If any problems are indicated, check the TDM cables in the associated EPN.