
DEFINITY Enterprise Communications Server Release 6 | Issue 5 |
Installation and Test for | May 1998 |
|
|
5Install and Wire Telephones and Other Equipment
Add | Page |
Resolve Alarms
1.Examine the alarm log. Resolve any alarms that may exist using DEFINITY Enterprise Communications Server Release 6 Maintenance for R6r.
Contact INADS to Enable Customer Options and
Verify Alarm Origination
1.Be sure the system is part of the existing INADS database by calling the INADS Database Administrator at the Technical Service Center (TSC). Verify that INADS can dial into the system and that the system can dial out to INADS.
As part of the system registration process, the INADS Database Administrator enables Alarm Origination and enables customer options.
!
CAUTION:
If you do not enable Alarm Origination when the customer has purchased a services contract, the system cannot report any alarm to the TSC automatically, causing the TSC to be unable to fulfill the services contract.
Save Translations
1.If the system is high or critical reliability, enter status system 1 and press Enter to verify that the system is in the “active/standby” mode.
2.Enter save translation and press Enter. This instructs the system to take all translation information in memory and write it to the translation card or tape.
3.If the system contains a TN750/B Announcement circuit pack, enter list configuration
4.Update backup tape, if required.