DEFINITY Enterprise Communications Server Release 6

Issue 5

Installation and Test for Multi-Carrier Cabinets 555-230-112

May 1998

 

 

2Install Telecommunications Cabling

Cable Installation

Page 2-21

Connect Control Carrier Outputs Cable

Plug the connector cable in the AUX connector on the rear of the Control Carrier. Route the connector cable through the cable slack manager to the assigned 110-type terminal block in the yellow field of the trunk/auxiliary field.

Install Trunk Cables Among Network Interface,

Sneak Fuse Panel, and Cabinet

The 1-pair of Central Office (CO) trunks are installed by the network provider in the green field. Up to 24 pairs may be terminated on each row of the 110-type terminal block. Tie trunks also appear in the green field with up to eight 3-pair trunks terminated on each row of the 110-type terminal block.

Select Concentrator Cables

WP-90929, List 1 and 3 concentrator cables can be used to connect the cabinet to the 110-type terminal blocks in the purple field. The 1-pair patch cords/jumper wires are then run from the purple terminal block rows to the green terminal block rows in order to establish the correct 3-pair modularity.

Connect Trunk Pairs Using Concentrator Cables

Figure 2-12 shows trunk pairs connected to the cabinet with concentrator cables. To install the cables:

1.Connect B25A cables between the network interface and sneak fuse panels.

2.Connect A25D cables from the sneak fuse panels to the 110-type terminal block connectors in the green field.

3.Connect patch cords/jumper wires from the terminal block in the green field to the associated terminal block in the purple field.

4.Connect the single-fingered end of the concentrator cables to the 110-type terminal block connectors in the purple field in Step 3.

5.Connect the other end (2/3-fingered end) of the concentrator cables to the appropriate carrier slots. Equipped carrier slots are identified on the CSD. Mark the nomenclature strips above the carriers to identify the slots.

6.Label connectors on each end of the cables that connect to the cabinet.

7.Route the cables down the sides of the cabinet and store the excess cable slack in the cable slack manager as previously described.

Page 74
Image 74
Lucent Technologies Release 6 manual Connect Control Carrier Outputs Cable, Select Concentrator Cables