DEFINITY Enterprise Communications Server Release 6

Issue 5

Installation and Test for Multi-Carrier Cabinets 555-230-112

May 1998

 

 

5Install and Wire Telephones and Other Equipment

Connect External Alarm Indicators

Page 5-17

Connect External Alarm Indicators

Alarm Input

Alarms can be generated on adjunct equipment, sent to the DEFINITY System, and recorded and reported as “external alarms.” A typical major alarm input is from an Uninterruptible Power Supply (UPS).

1.Connect 1 major and 1 minor alarm input pair to the trunk/auxiliary field from the AUX connector. See Table 5-5.

Table 5-5. Alarm Inputs at AUX Connector

Color

AUX Connector

 

 

 

White-Blue

AP1 (Pin 26) Major Alarm Input

Blue-White

Ground (Pin 1)

 

 

 

White-Orange

AP2 (Pin 27) Minor Alarm Input

Orange-White

Ground (Pin 2)

 

 

 

 

 

 

Alarm Output

The system provides a relay contact that can operate a customer-provided alarm, such as a light or bell. The circuitry and power source are customer- provided. The alarm device must not exceed a rating of more than 30 VAC RMS or 60 VDC at 0.75 Amp.

1.Connect an external alarm output through pins 48 and 23 of the AUX connector. See Table 5-6.

2.Note which device connects to which alarm and give this information to your Lucent Technologies representative for troubleshooting purposes.

Table 5-6. Alarm Output at AUX Connector

Color

AUX Connector

 

 

 

 

 

 

Violet-Green

EXTALMA (Pin 48)

Alarm Output

Green-Violet

EXTALMB (Pin 23)

(Ground) Alarm Output

 

 

 

 

 

 

 

 