DEFINITY Enterprise Communications Server Release 6 | Issue 5 |
Installation and Test for | May 1998 |
|
|
5Install and Wire Telephones and Other Equipment
1145B Power Supply | Page |
Wall-Mounting Plates
The top plate is used for mounting the
1.Locate 1 plate directly below the other such that the AC power cord (6.5 feet or 2 meters) reaches the electrical outlet from a power supply mounted on the bottom plate. Both plates should be located so the raised letters are right side up.
![]()
NOTE:
A maximum of 4 power supplies can be powered from 1 dedicated 110 VAC, 20 amp (or 230 VAC, 15 amp) feeder. Use only unswitched receptacles (receptacles not connected to a wall switch).
2.Secure the wall mounting plates to a standard 3/4 inch (2 cm) thick plywood mounting board. Each mounting plate comes with four #10 x
3.The 1145B Power Supply is
4.An
5.Mark the Unit Number and Connectivity information on the front label next to the LEDs.