1 Install and Connect Cabinets

 

Connect External Alarm Cable

Page 1-27

 

 

Connect External Alarm Cable

1.Plug the external alarm cable into the connector shown in Figure 1-9.

2.Route the opposite end of the cable to the MDF. The alarm cable is

connected to the MDF in Chapter 5, ‘Installand Wire Telephones and Other Equipment’.

Connect AC Power to Stratum 3 Clock

Cabinet

The clock cabinet requires a 120 VAC, 15 Amp receptacle. The green wire ground provided by the receptacle is sufficient. The clock cabinet does not require a ground connection back to the single-point ground.

Check Commercial Power and Connect AC Power

Before powering up the system, check the AC power using a KS-20599 digital voltmeter (DVM) (or equivalent).

1.Set the DVM to the 250 volt range.

2.Carefully measure the voltage between the hot and neutral side of the receptacle. The neutral wire is white, the hot wire is black.

3.Verify the meter reads 106 to 128 VAC. If not, have a qualified electrician correct the problem.

4.Measure the voltage between the neutral and ground side of the receptacle. The ground wire is green.

5.Verify the meter reads 0 VAC. If not, have a qualified electrician correct the problem.

6.Set all cabinet power modules OFF. Plug the AC power cable into the receptacle.