DEFINITY Enterprise Communications Server Release 6

Issue 5

Installation and Test for Multi-Carrier Cabinets 555-230-112

May 1998

1 Install and Connect Cabinets

 

 

Connect AC Power and Ground

Page 1-15

 

 

 

 

 

 

 

 

Figure Notes

 

1. Shorting Cable (H600-442-G1) (If

2. J11

Battery Charger is Not Installed)

 

Figure 1-5. Shorting Cable Installation

1.Set the circuit breakers on the power distribution unit OFF. See Figure 1-5.

2.At the rear of the cabinet, insert the shorting cable (H600-442-G1) into J11. The cable is keyed so it can fit only 1 way.

Connect AC Power

1.Set the main circuit breakers on the power distribution unit OFF.

2.Connect cabinet AC line cords to the AC power receptacles.

3.Do not power up the system at this time.

Page 32
Image 32
Lucent Technologies Release 6 manual Connect AC Power, Shorting Cable Installation