1Install and Connect Cabinets

Connect AC Power and Ground

Page 1-9

NOTE:

If the EPN cabinet is located remote from the PPN cabinet (in a separate room or building), connect the CABINET GROUND wire to an approved ground.

 

 

7

3

3

3

 

 

5

 

 

6

1

2

2

4

4

4

widmgrnd LJK 092697

Figure Notes

1.PPN Cabinet

2.EPN Cabinet (if Installed)

3.6 AWG (#40) (16 mm2) CABINET GROUND Wire

4.Cabinet Ground Terminal Block

5.AC Load Center Single-Point Ground

6.Less than 50 Wire Feet (15.2 m)

7.10 AWG (#25) (6 mm2) Ground Wire to CBC

Figure 1-1. Typical Cabinet Ground Location

5. Repeat connecting each EPN cabinet to the single-point ground block.