Measuring Single-Mode Power in the Field
The data pattern on the link influences the optical power measurement. The duty cycle that the transceiver is sending when the DEFINITY System is idle is a 30% on (“1”) and 70% off (“0”) data pattern. This implies that the optical reading will be about 2.3dB less than the typical output power specification
The following information is provided for field troubleshooting use only and is not intended for fiber budget analysis.
The power measurement is taken from the TX connector, through the entire fiber link, and to the RX connector on the opposite end of the link (remote EPN). Refer to Figure
1.Remove the fiber cable from the RX connector at the local 300A.
2.Attach the power meter to the fiber cable. Note the reading.
3.Reconnect the RX cable.
4.Repeat the test at the RX connector at the remote 300A. Note the reading.
5.Reconnect the RX cable.
6.Using Figure
![]()
NOTE:
Using the maximum power budget of 17dB in any fiber link may cause problems if the fiber plant is damaged and additional connectors or splices are added. Maintain a margin of at least 1dB; 2dB is the industry standard.