DEFINITY Enterprise Communications Server Release 6 | Issue 5 |
Installation and Test for | May 1998 |
1 Install and Connect Cabinets |
|
Connect DC Power and Ground | Page |
|
|
Mixed AC/DC Power and Ground
Figure 1-8 shows a power and ground layout for a mixed AC/DC-powered cabinet configuration in the same equipment room with the PPN being DC powered and the EPN being AC powered. If a second EPN is part of the system, use the same basic connections shown in Figure 1-8.
Approved
ground
Ground | 75A | |
discharge | ||
| ||
bar | ||
|
System
DC power supply
Coupled Bonding Conductor
1/0 AWG (50 mm2) up to 50 feet (15.2 m) or engineered for less than 0.5 voltage drop per conductor
To
AC power
source
| PPN |
| EPN | |
| cabinet |
| cabinet | |
|
| AC power cord | ||
|
| AC power- | ||
|
| distribution | ||
| unit | |||
|
|
| ||
|
|
|
|
|
|
|
|
|
|
Cabinet Ground Block
To CBC terminal block at MDF
cydfacdc RPY 021798