DEFINITY Enterprise Communications Server Release 6

Issue 5

Installation and Test for Multi-Carrier Cabinets 555-230-112

May 1998

1 Install and Connect Cabinets

 

Connect DC Power and Ground

Page 1-22

 

 

Mixed AC/DC Power and Ground

Figure 1-8 shows a power and ground layout for a mixed AC/DC-powered cabinet configuration in the same equipment room with the PPN being DC powered and the EPN being AC powered. If a second EPN is part of the system, use the same basic connections shown in Figure 1-8.

Approved

ground

Ground

75A

discharge

 

bar

-48V

 

System single-point ground

DC power supply

Coupled Bonding Conductor

1/0 AWG (50 mm2) up to 50 feet (15.2 m) or engineered for less than 0.5 voltage drop per conductor

To

AC power

source

 

PPN

 

EPN

 

cabinet

 

cabinet

 

 

AC power cord

 

 

AC power-

 

 

distribution

-48V

-48V RTN

 

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Cabinet Ground Block

To CBC terminal block at MDF

cydfacdc RPY 021798

Figure 1-8. Typical Power and Ground for a Mixed AC/DC-Powered Cabinet

Page 39
Image 39
Lucent Technologies Release 6 Mixed AC/DC Power and Ground, Typical Power and Ground for a Mixed AC/DC-Powered Cabinet