DEFINITY Enterprise Communications Server Release 6

Issue 5

Installation and Test for Multi-Carrier Cabinets 555-230-112

May 1998

 

 

2Install Telecommunications Cabling

Cable Installation

Page 2-24

 

 

 

3

1

2

3

4

5

6

7

8

9

10 11 12

13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

r758537b MMR 031496

Figure Notes:

 

 

1.

Green Field

3.

Pairs

2.

1-Pair Jumpers

4.

Purple Field

Figure 2-14. 3-Pair Modularity for Trunk Pairs for 3-Pair Tie Trunks

Install Cables Between Cabinet and MDF

1.Install “D” rings on the wall between the cable slack manager and the terminal/connecting blocks mounted on the MDF.

2.Install a self-adhesive port label on the back of each connector on the connector cable. Labels should be positioned so they are not covered by the cabinet connector retainers.

3.At the rear of the cabinet, connect 1 end of the connector cable to the assigned connector.

4.Route the cable down the rear of the cabinet, through the cable slack manager, and to the MDF.

5.At the MDF, connect the other end of the cable to the assigned terminal/ connecting block connector.

6.Store the cable slack in the cable slack manager.

7.Repeat Steps 2 through 6 until all cables are installed.

Page 77
Image 77
Lucent Technologies Release 6 manual Install Cables Between Cabinet and MDF