DEFINITY Enterprise Communications Server Release 6 | Issue 5 |
Installation and Test for | May 1998 |
1 Install and Connect Cabinets |
|
Connect Remote Power Off Cable and External Alarm Cable | Page |
|
|
Connect Remote Power Off Cable and
External Alarm Cable
Figure 1-9 shows the location of the Remote Power Off (RPO) cable. The opposite end of the cable connects to the Emergency Power Off (EPO) switch located outside of the equipment room.
Carrier
circuit
breakers
Connect RPO cable here (J21)
Connect external alarm cable here (J18)
![]()
Pin 6
![]()
Pin 2 (+RPO)
| External |
psdf002 CJL 081596 | alarm cable |
Figure 1-9. Remote Power Off Cable Connections — Part 1
Even though the equipment room EPO switch disconnects main AC power to the equipment room, it cannot disconnect the battery power from the J58890CH. An auxiliary set of contacts inside the EPO are used for this function.
1.Plug the RPO cable into the connector shown in Figure
2.Route the opposite end of the wires to the EPO switch. The opposite end of the RPO cable connects to the internal relay.
![]()
NOTE:
The EPO switch and the auxiliary contacts (inside the EPO switch assembly) are