Parameter Description

Issue 01/06

P0821

BI: DDS bit 1

 

 

Min:

0:0

 

CStat:

CT

Datatype: U32

Unit: -

Def:

0:0

 

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4095:0

Level

3

Selects command source from which Bit 1 for selecting a drive data set is to be read in (see parameter P0820).

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

Note:

P0820 is also relevant for drive data set (DDS) selection.

3.14BICO command parameters

P0840[3] BI: ON/OFF1

 

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

722:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Allows ON/OFF1 command source to be selected using BICO.

Level

3

The first three digits describe the parameter number of the command source; the last digit denotes the bit setting for that parameter. The default setting (ON right) is digital input 1 (722.0). Alternative source possible only when function of digital input 1 is changed (via P0701) before changing value of P0840.

ON

OFF1

t

 

 

f

 

 

 

 

 

 

 

f max

 

 

f act,motor

 

 

 

 

(P1082)

 

 

 

 

f 2

 

P2168

f act,inverter

 

 

 

 

 

P2167

 

 

 

 

0

P2168

t

 

 

 

tdown,OFF1 =

P1121

f 2

 

tdown,OFF1

 

P1082

P1120

P1121

 

 

 

 

 

r0052 Bit02

 

 

 

 

Operation

Pulse cancellation

Index:

t

P0840[0] : 1st. Command data set (CDS)

P0840[1] : 2nd. Command data set (CDS)

P0840[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

19.0= ON/OFF1 via BOP

Dependency:

Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).

Note:

- OFF1 means a ramp stop down to 0 using P1121. - OFF1 is low active.

- For the priority of all soft commands, the following applies: OFF2, OFF3, OFF1

102

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0