Issue 01/06

Parameter Description

P0842[3] BI: ON reverse/OFF1

 

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

0:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Allows ON/OFF1 reverse command source to be selected using BICO.

Level

3

Normally in this case at a positive frequency setpoint, it is getting approached ccw (negative frequency setpoint) The first three digits describe the parameter number of the command source and the last digit denotes the bit setting for that parameter.

Index:

P0842[0] : 1st. Command data set (CDS)

P0842[1] : 2nd. Command data set (CDS)

P0842[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

19.0= ON/OFF1 via BOP

Details:

See parameter P0840.

P0844[3] BI: 1. OFF2

 

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

1:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines first source of OFF2.

Level

3

The first three digits describe the parameter number of the command source and the last digit denotes the bit setting for that parameter. If one of the digital inputs is selected for OFF2, the inverter will not run unless the digital input is active.

f act

P1082

fmax

r0052 Bit02

Operation

Pulse cancellation

Index:

OFF2

f act,motor

t

fact,inverter

t

P0844[0] : 1st. Command data set (CDS)

P0844[1] : 2nd. Command data set (CDS)

P0844[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

19.0= ON/OFF1 via BOP

19.1= OFF2: Electrical stop via BOP

Dependency:

Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).

Note:

- OFF2 means an immediate pulse inhibit; the motor coasts down. - OFF2 is low active.

- The following applies for the priority of all of the OFF commands: OFF2, OFF3, OFF1

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

103