Siemens 440 manual Communication parameters, P08493 BI 2. OFF3, P08523 BI Pulse enabling

Models: 440

1 328
Download 328 pages 28.01 Kb
Page 105
Image 105

Issue 01/06

Parameter Description

P0849[3] BI: 2. OFF3

 

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

1:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines second source of OFF3.

Level

3

The first three digits describe the parameter number of the command source and the last digit denotes the bit setting for that parameter. If one of the digital inputs is selected for OFF3, the inverter will not run unless the digital input is active.

Index:

P0849[0] : 1st. Command data set (CDS)

P0849[1] : 2nd. Command data set (CDS)

P0849[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

19.0= ON/OFF1 via BOP

Dependency:

In contrast to P0848 (first source of OFF3), this parameter is always active, independent of P0719 (selection of command and frequency setpoint).

Details:

See parameter P0848.

P0852[3] BI: Pulse enabling

 

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

1:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines source of pulse enable/disable signal.

Index:

P0852[0] : 1st. Command data set (CDS)

P0852[1] : 2nd. Command data set (CDS)

P0852[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

Dependency:

Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).

3.15Communication parameters

Level

3

P0918

CB address

 

 

Min:

0

 

CStat:

CT

Datatype: U16

Unit: -

Def:

3

 

P-Group:

COMM

Active: first confirm

QuickComm.: No

Max:

65535

Defines address of CB (communication board) or address of the other option modules.

There are two ways to set the bus address:

-via DIP switches on the PROFIBUS module

-via a user-entered value

Level

2

Note:

Possible PROFIBUS settings:

-1 ... 125

-0, 126, 127 are not allowed

The following applies when a PROFIBUS module is used:

-

DIP switch

= 0

Address defined in P0918 (CB address) is valid

-

DIP switch not

= 0

DIP switch setting has priority and P0918 indicates DIP switch setting.

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

105

Page 105
Image 105
Siemens 440 manual Communication parameters, P08493 BI 2. OFF3, P08523 BI Pulse enabling, P0918 CB address