Siemens 440 manual R06333 CO Rotor winding temperature, P06403 Motor overload factor %

Models: 440

1 328
Download 328 pages 28.01 Kb
Page 74
Image 74

Parameter Description

Issue 01/06

r0633[3]

CO: Rotor winding temperature

 

Min:

-

 

Datatype: Float

Unit: °C

Def:

-

 

P-Group: MOTOR

 

Max:

-

Level

4

Displays rotor winding temperature of motor mass model.

Index:

 

r0633[0]

: 1st. Drive data set (DDS)

r0633[1]

: 2nd. Drive data set (DDS)

r0633[2]

: 3rd. Drive data set (DDS)

P0640[3] Motor overload factor [%]

 

Min:

10.0

Level

 

CStat:

CUT

Datatype: Float

Unit: %

Def:

150.0

2

 

 

 

P-Group:

MOTOR

Active: Immediately

QuickComm.: Yes

Max:

400.0

 

Defines motor overload current limit in [%] relative to P0305 (rated motor current).

Index:

P0640[0] : 1st. Drive data set (DDS)

P0640[1] : 2nd. Drive data set (DDS)

P0640[2] : 3rd. Drive data set (DDS)

Dependency:

Limited to maximum inverter current or to 400 % of rated motor current (P0305), whichever is the lower.

P0640max =

min(r0209,4 P0305)

100

P0305

 

 

Details:

See function diagram for current limitation.