Parameter Description | Issue 01/06 |
3.30Inverter parameters (Modulator)
P1800 | Pulse frequency |
|
| Min: | 2 | |
| CStat: | CUT | Datatype: U16 | Unit: kHz | Def: | 4 |
| INVERTER | Active: Immediately | QuickComm.: No | Max: | 16 |
Level
2
Sets pulse frequency of power switches in inverter. The frequency can be changed in steps of 2 kHz.
Dependency:
Minimum pulse frequency depends on P1082 (maximum frequency) and P0310 (rated motor frequency).
-see derating in P1082
-P1800 > 30 * P0310
Note:
-If the pulse frequency is increased, max. inverter current r0209 can be reduced (derating). The derating characteristic depends on the type and power of the inverter (see manuall OPERATING INSTRUCTION).
-If silent operation is not absolutely necessary, lower pulse frequencies may be selected to reduce inverter losses and
-Under certain circumstances, the inverter may reduce the switching frequency to provide protection against
r1801 | CO: Act. pulse frequency |
| Min: | - | Level |
| Datatype: U16 | Unit: kHz | Def: | - | 3 |
|
| ||||
|
|
| Max: | - |
|
Actual pulse frequency of power switches in inverter.
Notice:
Under certain conditions (inverter overtemperature, see P0290), this can differ from the values selected in P1800 (pulse frequency).
P1802 | Modulator mode |
|
| Min: | 0 | |
| CStat: | CUT | Datatype: U16 | Unit: - | Def: | 0 |
| INVERTER | Active: first confirm | QuickComm.: No | Max: | 2 |
Level
3
Selects inverter modulator mode.
Possible Settings:
0SVM/ASVM automatic mode
1Asymmetric SVM
2Space vector modulation
Notice:
-Asymmetric space vector modulation (ASVM) produces lower switching losses than space vector modulation (SVM), but may cause irregular rotation at very low frequencies.
-Space vector modulation (SVM) with
-Space vector modulation (SVM) without
P1803[3] Max. modulation |
|
| Min: | 20.0 | |
CStat: | CUT | Datatype: Float | Unit: % | Def: | 106.0 |
INVERTER | Active: Immediately | QuickComm.: No | Max: | 150.0 |
Level
4
Sets maximum modulation index.
Index:
P1803[0] : 1st. Drive data set (DDS)
P1803[1] : 2nd. Drive data set (DDS)
P1803[2] : 3rd. Drive data set (DDS)
Note:
-P1803 = 100 % : Limit for
-For vector control the modulation limit will be reduced automatically with 4 %.
P1820[3] Reverse output phase sequence |
| Min: | 0 | ||
CStat: | CT | Datatype: U16 | Unit: - | Def: | 0 |
INVERTER | Active: first confirm | QuickComm.: No | Max: | 1 |
Level
2
Changes direction of motor rotation without changing setpoint polarity.
Possible Settings:
0OFF
1ON
Index:
P1820[0] : 1st. Drive data set (DDS)
P1820[1] : 2nd. Drive data set (DDS)
P1820[2] : 3rd. Drive data set (DDS)
Dependency:
If positive and negative revolution is enabled, frequency setpoint is directly used.
If both positive and negative revolution are disabled, reference value is set to zero.
Details:
See P1000 (select frequency setpoint)
188 | MICROMASTER 440 Parameter List |