Parameter Description

Issue 01/06

r2018[8] CO: PZD from COM link (USS)

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: COMM

 

Max:

-

 

Displays process data received via USS on COM link.

 

 

 

Level

3

PZD4

PZD3

PZD2

PZD1

STW2

 

HSW

STW1

 

 

P2012

 

BCC

 

PZD

PKW

 

ADR

 

LGE

 

STX

 

Process data

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

USS telegram

r2018

 

 

[0]

r2036

 

[1]

 

 

[2]

 

.

[3]

 

 

 

.

 

r2037

.

[7]

 

 

STX

Start of text

 

LGE

Length

 

ADR

Address

 

PKW

Parameter ID value

PZD

Process data

 

BCC

Block check character

STW

Control word

 

HSW

Main setpoint

 

USS on COM link PZD mapping to parameter r2018

Index:

r2018[0] : Received word 0

r2018[1] : Received word 1

r2018[2] : Received word 2

r2018[3] : Received word 3

r2018[4] : Received word 4

r2018[5] : Received word 5

r2018[6] : Received word 6

r2018[7] : Received word 7

Note:

The control words can be viewed as bit parameters r2036 and r2037.

Restrictions:

-If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be transferred in the 1st PZD-word.

-If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the 2nd PZD-word,

-When P2012 is greater than or equal to 4 the additional control word (2nd control word) must transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719).

200

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 200
Image 200