Parameter Description

3.34Communication parameters (USS, CB)

P2009[2]

USS denormalization

 

 

Min:

0

 

CStat:

CT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

COMM

Active: first confirm

QuickComm.: No

Max:

1

Level

3

Enables denormalization for USS.

Possible Settings:

0Disabled

1Enabled

Index:

P2009[0] : Serial interface COM link

P2009[1] : Serial interface BOP link

Note:

If denormalization is enabled, the main setpoint (word 2 in PZD) is not interpreted as 100 % = 4000H, but as "absolute" instead (e.g. 4000H = 16384 means 163.84 Hz ) if this is a frequency. Denormalization (P2009 = 1) only works for frequencies and is intended for backwards compatibility with MM3.

P2010[2] USS baudrate

 

 

Min:

4

CStat:

CUT

Datatype: U16

Unit: -

Def:

6

P-Group:

COMM

Active: first confirm

QuickComm.: No

Max:

12

Level

2

Sets baud rate for USS communication.

Possible Settings:

42400 baud

54800 baud

69600 baud

719200 baud

838400 baud

957600 baud

1076800 baud

1193750 baud

12115200 baud

Index:

P2010[0] : Serial interface COM link

P2010[1] : Serial interface BOP link

P2011[2] USS address

 

 

Min:

0

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

P-Group:

COMM

Active: first confirm

QuickComm.: No

Max:

31

Level

2

Sets unique address for inverter.

Index:

P2011[0] : Serial interface COM link

P2011[1] : Serial interface BOP link

Note:

You can connect up to a further 30 inverters via the serial link (i.e. 31 inverters in total) and control them with the USS serial bus protocol.

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

195