Parameter Description

Issue 01/06

P1312[3] Starting boost

 

 

Min:

0.0

CStat:

CUT

Datatype: Float

Unit: %

Def:

0.0

P-Group:

CONTROL

Active: Immediately

QuickComm.: No

Max:

250.0

Level

2

Applies a constant linear offset (in [%] relative to P0305 (rated motor current)) to active V/f curve (either linear or quadratic) after an ON command and is active until

1)ramp output reaches setpoint for the first time respectively

2)setpoint is reduced to less than present ramp output

This is useful for starting loads with high inertia.

Setting the starting boost (P1312) too high will cause the inverter to limit the current, which will in turn restrict the output frequency to below the setpoint frequency.

V

Boost voltage

Validity range

Vmax

 

 

 

 

 

 

 

 

 

 

Vn

 

 

 

 

 

 

 

 

 

ON

(P0304)

actual VBoost

 

 

 

 

 

e

OFF

 

 

 

 

 

g

 

 

 

 

 

 

 

ta

 

 

 

 

 

 

 

 

 

l

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

v

 

 

 

f

 

 

t

 

 

 

 

 

 

 

 

u

 

 

 

f

 

 

 

 

p

 

 

 

 

 

 

VStartBoost,100

t

 

 

 

 

/

 

 

u

 

 

 

V

 

)

 

O

 

 

 

 

l

 

 

 

 

 

 

 

 

a

 

0

 

 

 

 

m

 

=

 

 

 

 

r

 

0

 

 

 

 

 

o

 

 

 

 

 

 

 

N

 

 

0

 

 

 

 

 

 

3

 

 

 

P1312 active

 

 

 

1

 

 

 

 

 

 

(P

 

 

 

 

 

VStartBoost,50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

0

0

fBoost,end

 

 

 

 

 

 

 

 

f

 

 

 

 

 

 

 

fn

fmax

 

(P1316)

 

 

 

 

 

 

 

(P0310)

(P1082)

t

t

t

where voltage values are given

VStartBoost,100 = P0305P0350P1312

100

=VStartBoost,100

VStartBoost,502

Index:

P1312[0] : 1st. Drive data set (DDS)

P1312[1] : 2nd. Drive data set (DDS)

P1312[2] : 3rd. Drive data set (DDS)

Example:

Setpoint = 50Hz. Ramping up with starting boost. During ramp up, setpoint changed to 20Hz. As soon as setpoint changed, starting boost removed because setpoint smaller than present ramp output.

Dependency:

Acceleration boost P1312 has no effect during vector operation.

Note:

See parameter P1310

r1315

CO: Total boost voltage

 

Min:

-

 

Datatype: Float

Unit: V

Def:

-

 

P-Group: CONTROL

 

Max:

-

Displays total value of voltage boost (in volts).

Level

4

158

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0