Parameter Description | Issue 01/06 |
P1312[3] Starting boost |
|
| Min: | 0.0 | |
CStat: | CUT | Datatype: Float | Unit: % | Def: | 0.0 |
CONTROL | Active: Immediately | QuickComm.: No | Max: | 250.0 |
Level
2
Applies a constant linear offset (in [%] relative to P0305 (rated motor current)) to active V/f curve (either linear or quadratic) after an ON command and is active until
1)ramp output reaches setpoint for the first time respectively
2)setpoint is reduced to less than present ramp output
This is useful for starting loads with high inertia.
Setting the starting boost (P1312) too high will cause the inverter to limit the current, which will in turn restrict the output frequency to below the setpoint frequency.
V | Boost voltage | Validity range | ||||||||
Vmax |
|
|
|
|
|
|
|
|
|
|
Vn |
|
|
|
|
|
|
|
|
| ON |
(P0304) | actual VBoost |
|
|
|
|
| e | OFF | ||
|
|
|
|
| g |
|
| |||
|
|
|
|
| ta |
|
| | ||
|
|
|
|
|
| l |
|
|
| |
|
|
|
|
| o |
|
|
| ||
|
|
| v |
|
|
| f | |||
|
| t |
|
|
|
|
|
| ||
|
| u |
|
|
| f |
|
| ||
|
| p |
|
|
|
|
|
| ||
VStartBoost,100 | t |
|
|
|
| / |
|
| ||
u |
|
|
| V |
| ) |
| |||
O |
|
|
|
| l |
|
|
| ||
|
|
|
|
| a |
| 0 |
| ||
|
|
| m |
| = |
|
| |||
|
| r |
| 0 |
|
|
| |||
|
| o |
|
|
|
|
| |||
|
| N |
|
| 0 |
|
|
| ||
|
|
| 3 |
|
|
| P1312 active | |||
|
|
| 1 |
|
|
|
| |||
|
| (P |
|
|
|
|
| |||
VStartBoost,50 |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| 1 | |
|
|
|
|
|
|
|
|
|
| 0 |
0 | fBoost,end |
|
|
|
|
|
|
|
| f |
|
|
|
|
|
|
| fn | fmax | ||
| (P1316) |
|
|
|
|
|
|
| (P0310) | (P1082) |
t
t
t
where voltage values are given
VStartBoost,100 = P0305⋅ P0350⋅ P1312
100
=VStartBoost,100
VStartBoost,502
Index:
P1312[0] : 1st. Drive data set (DDS)
P1312[1] : 2nd. Drive data set (DDS)
P1312[2] : 3rd. Drive data set (DDS)
Example:
Setpoint = 50Hz. Ramping up with starting boost. During ramp up, setpoint changed to 20Hz. As soon as setpoint changed, starting boost removed because setpoint smaller than present ramp output.
Dependency:
Acceleration boost P1312 has no effect during vector operation.
Note:
See parameter P1310
r1315 | CO: Total boost voltage |
| Min: | - |
| Datatype: Float | Unit: V | Def: | - |
|
| Max: | - |
Displays total value of voltage boost (in volts).
Level
4
158 | MICROMASTER 440 Parameter List |