Parameter Description | Issue 01/06 |
P0625[3] Ambient motor temperature |
| Min: | |||
CStat: | CUT | Datatype: Float | Unit: °C | Def: | 20.0 |
MOTOR | Active: Immediately | QuickComm.: No | Max: | 80.0 |
Level
3
Ambient temperature of motor. The parameter for the stator resistance P0350 and rotor resistance P0354 relate to the ambient temperature.
P0626 | P0627 | P0628 | P0304 | P0305 | P0307 | P0308 | P0310 | P0311 |
P0625
Thermal motor model
r0630
r0631
r0632
r0633
Equivalent
circuit
P1910
Index:
P0625[0] : 1st. Drive data set (DDS)
P0625[1] : 2nd. Drive data set (DDS)
P0625[2] : 3rd. Drive data set (DDS)
Note:
Following items should be considered when using P0625:
-The ambient temperature has to be entered prior to motor data identification.
-An accuracy of +/- 5°C is adequate.
-The motor data identification should be carried out on a cold motor (ambient temperature = stator temperature = rotor temperature).
-The highest accuracy at temperature adaption of the stator resistance and rotor resistance can be achieved by connecting a KTY84 sensor.
P0626[3] Overtemperature stator iron |
| Min: | 20.0 | Level | |||
| CStat: | CUT | Datatype: Float | Unit: °C | Def: | 50.0 | 4 |
| MOTOR | Active: Immediately | QuickComm.: No | Max: | 200.0 |
|
Overtemperature of stator iron.
Index:
P0626[0] : 1st. Drive data set (DDS)
P0626[1] : 2nd. Drive data set (DDS)
P0626[2] : 3rd. Drive data set (DDS)
Note:
See parameter P0627