Parameter Description

Issue 01/06

P2235[3] BI: Enable PID-MOP (UP-cmd)

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

19:13

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines source of UP command.

Index:

P2235[0] : 1st. Command data set (CDS)

P2235[1] : 2nd. Command data set (CDS)

P2235[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

19.D = Keypad UP button

Dependency:

To change setpoint:

1.Use UP / DOWN key on BOP or

2.Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3)

Level

3

P2236[3] BI: Enable PID-MOP (DOWN-cmd)

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

19:14

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines source of DOWN command.

Index:

P2236[0] : 1st. Command data set (CDS)

P2236[1] : 2nd. Command data set (CDS)

P2236[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

19.E = Keypad DOWN button

Dependency:

To change setpoint:

1.Use UP / DOWN key on BOP or

2.Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3)

Level

3

P2240[3] Setpoint of PID-MOP

 

 

Min:

-200.00

CStat:

CUT

Datatype: Float

Unit: %

Def:

10.00

P-Group:

TECH

Active: Immediately

QuickComm.: No

Max:

200.00

Level

2

Setpoint of the motor potentiometer.

Allows user to set a digital PID setpoint in [%].

Index:

P2240[0] : 1st. Drive data set (DDS)

P2240[1] : 2nd. Drive data set (DDS)

P2240[2] : 3rd. Drive data set (DDS)

Note:

P2240 = 100 % corresponds to 4000 hex

230

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 230
Image 230
Siemens 440 manual P22353 BI Enable PID-MOP UP-cmd, P22363 BI Enable PID-MOP DOWN-cmd, P22403 Setpoint of PID-MOP, 230