Issue 01/06 | Parameter Description |
P0040 | Reset energy consumption meter |
| Min: | 0 | ||
| CStat: | CT | Datatype: U16 | Unit: - | Def: | 0 |
| INVERTER | Active: first confirm | QuickComm.: No | Max: | 1 |
Resets value of parameter r0039 (energy consumption meter) to zero.
Possible Settings:
0No reset
1Reset r0039 to 0
Dependency:
No reset until "P" is pressed.
Level
2
r0050 | CO: Active command data set |
| Min: | - |
| Datatype: U16 | Unit: - | Def: | - |
|
| Max: | - |
Level
2
Displays currently selected and active command data set (CDS).
Possible Settings:
01st. Command data set (CDS)
12nd. Command data set (CDS)
23rd. Command data set (CDS)
Details:
See parameter P0810.
r0051[2] | CO: Active drive data set (DDS) |
| Min: | - |
| Datatype: U16 | Unit: - | Def: | - |
|
| Max: | - |
Displays currently selected and active drive data set (DDS).
Possible Settings:
01st. Drive data set (DDS)
12nd. Drive data set (DDS)
23rd. Drive data set (DDS)
Index:
r0051[0] : Selected drive data set
r0051[1] : Active drive data set
Details:
See parameter P0820.
Level
2
MICROMASTER 440 | Parameter List |
33 |