Issue 01/06

Parameter Description

P0040

Reset energy consumption meter

 

Min:

0

 

CStat:

CT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

INVERTER

Active: first confirm

QuickComm.: No

Max:

1

Resets value of parameter r0039 (energy consumption meter) to zero.

Possible Settings:

0No reset

1Reset r0039 to 0

Dependency:

No reset until "P" is pressed.

Level

2

r0050

CO: Active command data set

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: COMMANDS

 

Max:

-

Level

2

Displays currently selected and active command data set (CDS).

Possible Settings:

01st. Command data set (CDS)

12nd. Command data set (CDS)

23rd. Command data set (CDS)

Details:

See parameter P0810.

r0051[2]

CO: Active drive data set (DDS)

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: COMMANDS

 

Max:

-

Displays currently selected and active drive data set (DDS).

Possible Settings:

01st. Drive data set (DDS)

12nd. Drive data set (DDS)

23rd. Drive data set (DDS)

Index:

r0051[0] : Selected drive data set

r0051[1] : Active drive data set

Details:

See parameter P0820.

Level

2

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

33

Page 33
Image 33