Siemens 440 manual 154, ParNo Parameter name Level, Slvc, P1300 =

Models: 440

1 328
Download 328 pages 28.01 Kb
Page 154
Image 154

Parameter Description

Issue 01/06

P1300 = 19 : V/f control with independent voltage setpoint

The following table presents an overview of control parameters (V/f) that can be modify in relationship to

P1300 dependencies:

ParNo.

Parameter name

Level

 

 

 

 

V/f

 

 

 

 

 

 

SLVC

VC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P1300 =

 

 

 

 

 

 

 

 

 

0

1

2

3

 

 

5

 

6

19

20

 

22

21

 

23

P1300[3]

Control mode

2

x

x

x

 

x

 

 

x

 

x

x

x

 

x

x

 

x

P1310[3]

Continuous boost

2

x

x

x

 

x

 

 

x

 

x

x

 

 

P1311[3]

Acceleration boost

2

x

x

x

 

x

 

 

x

 

x

x

 

 

P1312[3]

Starting boost

2

x

x

x

 

x

 

 

x

 

x

x

 

 

P1316[3]

Boost end frequency

3

x

x

x

 

x

 

 

x

 

x

x

 

 

P1320[3]

Programmable V/f freq. coord. 1

3

 

x

 

 

 

 

 

P1321[3]

Programmable V/f volt. coord. 1

3

 

x

 

 

 

 

 

P1322[3]

Programmable V/f freq. coord. 2

3

 

x

 

 

 

 

 

P1323[3]

Programmable V/f volt. coord. 2

3

 

x

 

 

 

 

 

P1324[3]

Programmable V/f freq. coord. 3

3

 

x

 

 

 

 

 

P1325[3]

Programmable V/f volt. coord. 3

3

 

x

 

 

 

 

 

P1330[3]

CI: Voltage setpoint

3

 

 

 

x

 

 

P1333[3]

Start frequency for FCC

3

x

 

 

 

 

x

 

 

 

P1335[3]

Slip compensation

2

x

x

x

 

x

 

 

 

 

 

P1336[3]

CO: U/f Slip limit

2

x

x

x

 

x

 

 

 

 

 

P1338[3]

Resonance damping gain V/f

3

x

x

x

 

x

 

 

 

 

 

P1340[3]

Imax freq. controller prop. gain

3

x

x

x

 

x

 

 

x

 

x

x

 

 

P1341[3]

Imax controller integral time

3

x

x

x

 

x

 

 

x

 

x

x

 

 

P1345[3]

Imax controller prop. gain

3

x

x

x

 

x

 

 

x

 

x

x

 

 

P1346[3]

Imax voltage ctrl. integral time

3

x

x

x

 

x

 

 

x

 

x

x

 

 

P1350[3]

Voltage soft start

3

x

x

x

 

x

 

 

x

 

x

x

 

 

SLVC / VC can provide excellent performance for the following types of application:

-Applications which require high torque performance

-Applications which require fast respond to shock loading

-Applications which require torque holding while passing through 0 Hz

-Applications which require very accurate speed holding

-Applications which require motor pull out protection

SLVC/VC-Restrictions:

-SLVC / VC is dependent on the accuracy of the motor model being used and the measurements being performed by the inverter. There are therefore certain restrictions on the use of SLVC / VC:

fmax = min(200 Hz, 5 P0310)

(max. frequency)

 

1

P0305

r0209

(ratio of rated motor current to rated inverter current)

4

r0207

r0207

 

 

 

no synchronuos motor

Recommended means of SLVC/VC-commissioning:

-For correct operation under SLVC / VC control it is imperative that the name plate data of the motor (P0304 - P0310) is correctly entered and that the motor data identification (P1910) must be carried out on a cold motor. It is also necessary to ensure that the motor ambient temperature is correctly entered in P0625 if this is significantly different from the default value of 20°C. This must be done after the quick commissioning has been completed (P3900) but before the motor data identification measurements are carried out.

-See parameter P0400 and documentation of encoder and encoder module when commissioning VC (P1300 = 21 or 23).

SLVC/VC-Optimisation:

The following parameters can be adjusted by the user to improve performance. - P0003 = 3

 

- P0342: Total / motor inertia ratio

 

Sensorless Vector Control (SLVC):

 

- P1470: P gain (SLVC)

 

- P1472: I term (SLVC)

 

- P1610: Continuous torque boost (SLVC, open loop boost)

 

- P1611: Acceleration torque boost (SLVC, open loop boost)

 

- P1750: Control word of motor model

 

- P1755: Start-frequency motor model (SLVC)

154

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 154
Image 154