Issue 01/06

Parameter Description

Index:

P1000[0] : 1st. Command data set (CDS)

P1000[1] : 2nd. Command data set (CDS)

P1000[2] : 3rd. Command data set (CDS)

Example:

Setting 12 selects main setpoint (2) derived from analog input with additional setpoint (1) taken from the motor potentiometer.

Example P1000

= 12 :

 

 

 

 

 

 

 

 

 

P1000 = 12

P1070

= 755

P1070

CI: Main setpoint

 

 

 

r0755

CO: Act. ADC after scal. [4000h]

 

 

 

 

 

 

 

 

P1000 = 12

P1075

= 1050

P1075

CI: Additional setpoint

 

 

 

r1050

CO: Act. Output freq. of the MOP

 

 

 

 

 

 

 

 

 

MOP

ADC

FF

USS

BOP link

USS COM link

CB COM link

ADC2

P1000 = 12

P1000 = 12

Additonal setpoint

Main

setpoint

Sequence control

Setpoint

 

 

Motor

channel

 

 

control

 

 

 

 

 

Caution:

Be aware, by changing of parameter P1000 all BICO parameters (see table below) are modified.

Note:

Single digits denote main setpoints that have no additional setpoint.

Changing this parameter sets (to default) all settings on item selected (see table).

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

111

Page 111
Image 111
Siemens 440 manual 111, Example P1000