Parameter Description

3.29Control mode

P1300[3] Control mode

 

 

Min:

0

CStat:

CT

Datatype: U16

Unit: -

Def:

0

P-Group:

CONTROL

Active: first confirm

QuickComm.: Yes

Max:

23

Level

2

Controls relationship between speed of motor and voltage supplied by inverter as illustrated in the diagram below.

 

 

V

 

 

 

 

 

V

 

Vmax

 

 

 

 

 

 

 

r0071

 

 

 

 

 

Vn

 

Vn

 

 

 

 

 

 

P0304

 

 

 

 

 

 

 

 

P1300 = 3

 

 

 

 

 

 

 

 

 

P1300 = 0

P1325

 

 

 

 

 

 

P1323

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P1321

 

 

 

 

 

 

P1300 = 2

P1310

 

 

 

 

 

 

 

 

 

 

 

 

0

f

f0

f1

f2

f3

fn

f

fn

fmax

 

 

0 Hz

P1320 P1322

P1324 P0310

P1082

Possible Settings:

0V/f with linear characteristic

1V/f with FCC

2V/f with parabolic characteristic

3V/f with programmable characteristic

4Reserved

5V/f for textile applications

6V/f with FCC for textile applications

19V/f control with independent voltage setpoint

20Sensorless vector control

21Vector control with sensor

22Sensorless vector torque-control

23Vector torque-control with sensor

Index:

P1300[0] : 1st. Drive data set (DDS)

P1300[1] : 2nd. Drive data set (DDS)

P1300[2] : 3rd. Drive data set (DDS)

Dependency:

See parameter P0205, P0500

Caution:

When commissioning Vector Control with encoder-feedback (VC), the drive should be configured for V/f mode (see P1300) first. Run the drive and compare r0061 with r0021 that should agree in

-sign and

-magnitude (with a deviation of only a few percent).

Only if both criteria are fullfilled, change P1300 and select VC (P1300 = 21 or 23).

P0400 = 1 (single channel encoder) will only allow operation in one direction. If operation in both directions is required, connect an encoder with 2 channels (A and B) and select setting 2. See the Operating Instructions of the encoder module for more information.

Note:

P1300 = 1 : V/f with FCC (flux current control)

-Maintains motor flux current for improved efficiency.

-If FCC is chosen, linear V/f is active at low frequencies.

P1300 = 2 : V/f with a quadratic characteristic

-Suitable for centrifugal fans / pumps

P1300 = 3 : V/f with a programmable characteristic

-User defined characteristic (see P1320)

-For synchronous motors (e.g. SIEMOSYN motors)

P1300 = 5,6 : V/f for textil applications

-Slip compensation disabled.

-Imax controller modifies the output voltage only.

-Imax controller does not influence the output frequency.

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

153