Parameter Description

Issue 01/06

r2026[2]

USS character frame error

 

Min:

-

 

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: COMM

 

Max:

-

Index:

Displays number of USS character frame errors.

 

 

 

r2026[0]

: Serial interface COM link

 

 

 

 

 

 

 

 

r2026[1]

: Serial interface BOP link

 

 

 

Level

3

r2027[2] USS overrun error

 

Min:

-

Datatype: U16

Unit: -

Def:

-

P-Group: COMM

 

Max:

-

Level

3

Displays number of USS telegrams with overrun error.

Index:

r2027[0] : Serial interface COM link

r2027[1] : Serial interface BOP link

r2028[2] USS parity error

 

Min:

-

Datatype: U16

Unit: -

Def:

-

P-Group: COMM

 

Max:

-

Level

3

Displays number of USS telegrams with parity error.

Index:

r2028[0] : Serial interface COM link

r2028[1] : Serial interface BOP link

r2029[2]

USS start not identified

 

Min:

-

Level

 

 

Datatype: U16

Unit: -

Def:

-

3

 

 

 

 

P-Group: COMM

 

Max:

-

 

Index:

Displays number of USS telegrams with unidentified start.

 

 

 

r2029[0]

: Serial interface COM link

 

 

 

 

 

 

 

 

 

 

r2029[1]

: Serial interface BOP link

 

 

 

 

r2030[2] USS BCC error

 

Min:

-

Datatype: U16

Unit: -

Def:

-

P-Group: COMM

 

Max:

-

Level

3

Displays number of USS telegrams with BCC error.

Index:

r2030[0] : Serial interface COM link

r2030[1] : Serial interface BOP link

r2031[2] USS length error

 

Min:

-

Datatype: U16

Unit: -

Def:

-

P-Group: COMM

 

Max:

-

Level

3

Displays number of USS telegrams with incorrect length.

Index:

r2031[0] : Serial interface COM link

r2031[1] : Serial interface BOP link

r2032

BO: CtrlWrd1 from BOP link (USS)

 

Min:

-

Level

 

Datatype: U16

Unit: -

Def:

-

3

 

 

 

P-Group: COMM

 

Max:

-

 

Displays control word 1 from BOP link (word 1 within USS).

Bitfields:

 

 

 

 

 

Bit00

ON/OFF1

0

NO

1

YES

Bit01

OFF2: Electrical stop

0

YES

1

NO

Bit02

OFF3: Fast stop

0

YES

1

NO

Bit03

Pulses enabled

0

NO

1

YES

Bit04

RFG enable

0

NO

1

YES

Bit05

RFG start

0

NO

1

YES

Bit06

Setpoint enable

0

NO

1

YES

Bit07

Fault acknowledge

0

NO

1

YES

Bit08

JOG right

0

NO

1

YES

Bit09

JOG left

0

NO

1

YES

Bit10

Control from PLC

0

NO

1

YES

Bit11

Reverse (setpoint inversion)

0

NO

1

YES

Bit13

Motor potentiometer MOP up

0

NO

1

YES

Bit14

Motor potentiometer MOP down

0

NO

1

YES

Bit15

CDS Bit 0 (Local/Remote)

0

NO

1

YES

202

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 202
Image 202
Siemens 440 R20262 USS character frame error, R20272 USS overrun error, R20282 USS parity error, R20302 USS BCC error