Issue 01/06

Parameter Description

P2016[8] CI: PZD to BOP link (USS)

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

52:0

P-Group:

COMM

Active: Immediately

QuickComm.: No

Max:

4000:0

Selects signals (process data PZD) to be transmitted to serial interface via USS on BOP link

Level

3

r0052

P2016

 

 

 

 

r0052

[0]

 

 

 

 

r0021

[1]

 

 

 

 

 

[2]

 

 

 

 

r0053

[3]

 

 

 

 

r0053

.

 

 

 

 

 

.

PZD4

PZD3

PZD2

PZD1

 

.

 

[7]

ZSW2

 

HIW

ZSW1

STX

Start of text

LGE

Length

ADR

Address

PKW

Parameter ID value

PZD

Process data

BCC

Block check character

ZSW

Status word

HIW

Main actual value

BCC

P2012

PZD

 

PKW

Process data

 

Parameter

 

 

 

 

 

 

 

USS telegram

 

 

 

ADR LGE STX

PZD mapping from parameter P2016 USS on BOP link

Index:

P2016[0] : Transmitted word 0

P2016[1] : Transmitted word 1

P2016[2] : Transmitted word 2

P2016[3] : Transmitted word 3

P2016[4] : Transmitted word 4

P2016[5] : Transmitted word 5

P2016[6] : Transmitted word 6

P2016[7] : Transmitted word 7

Example:

P2016[0] = 52.0 (default). In this case, the value of r0052[0] (CO/BO: Status word) is transmitted as 1st PZD to the BOP link.

Note:

If r0052 not indexed, display does not show an index (".0" ).