Issue 01/06

Parameter Description

P1027[3] Fixed frequency mode - Bit 5

 

Min:

1

CStat:

CT

Datatype: U16

Unit: -

Def:

1

P-Group:

SETPOINT

Active: first confirm

QuickComm.: No

Max:

2

direct selection or direct selection + ON for bit 5

Possible Settings:

1Direct selection

2Direct selection + ON command

Index:

P1027[0] : 1st. Command data set (CDS)

P1027[1] : 2nd. Command data set (CDS)

P1027[2] : 3rd. Command data set (CDS)

Details:

See parameter P1001 for description of how to use fixed frequencies.

Level

3

P1028[3] BI: Fixed freq. selection Bit 5

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

722:5

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines origin of fixed frequency selection.

Index:

P1028[0] : 1st. Command data set (CDS)

P1028[1] : 2nd. Command data set (CDS)

P1028[2] : 3rd. Command data set (CDS)

Dependency:

Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO).

Details:

See P1020 (fixed frequency selection Bit 0) for most common settings.

Level

3

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

119

Page 119
Image 119