Parameter Description

P1017[3] Fixed frequency mode - Bit 1

 

Min:

1

CStat:

CT

Datatype: U16

Unit: -

Def:

1

P-Group:

SETPOINT

Active: first confirm

QuickComm.: No

Max:

3

Level

3

Fixed frequencies can be selected in three different modes. Parameter P1017 defines the mode of selection Bit 1.

Possible Settings:

1Direct selection

2Direct selection + ON command

3Binary coded selection + ON command

Index:

P1017[0] : 1st. Command data set (CDS)

P1017[1] : 2nd. Command data set (CDS)

P1017[2] : 3rd. Command data set (CDS)

Details:

See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.

P1018[3] Fixed frequency mode - Bit 2

 

Min:

1

CStat:

CT

Datatype: U16

Unit: -

Def:

1

P-Group:

SETPOINT

Active: first confirm

QuickComm.: No

Max:

3

Level

3

Fixed frequencies can be selected in three different modes. Parameter P1018 defines the mode of selection Bit 2.

Possible Settings:

1Direct selection

2Direct selection + ON command

3Binary coded selection + ON command

Index:

P1018[0] : 1st. Command data set (CDS)

P1018[1] : 2nd. Command data set (CDS)

P1018[2] : 3rd. Command data set (CDS)

Details:

See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.

P1019[3] Fixed frequency mode - Bit 3

 

Min:

1

CStat:

CT

Datatype: U16

Unit: -

Def:

1

P-Group:

SETPOINT

Active: first confirm

QuickComm.: No

Max:

3

Level

3

Fixed frequencies can be selected in three different modes. Parameter P1019 defines the mode of selection Bit 3.

Possible Settings:

1Direct selection

2Direct selection + ON command

3Binary coded selection + ON command

Index:

P1019[0] : 1st. Command data set (CDS)

P1019[1] : 2nd. Command data set (CDS)

P1019[2] : 3rd. Command data set (CDS)

Details:

See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.

P1020[3] BI: Fixed freq. selection Bit 0

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

0:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines origin of fixed frequency selection.

Index:

P1020[0] : 1st. Command data set (CDS)

P1020[1] : 2nd. Command data set (CDS)

P1020[2] : 3rd. Command data set (CDS)

Common Settings:

P1020 = 722.0 ==> Digital input 1

P1021 = 722.1 ==> Digital input 2

P1022 = 722.2 ==> Digital input 3

P1023 = 722.3 ==> Digital input 4

P1026 = 722.4 ==> Digital input 5

P1028 = 722.5 ==> Digital input 6

Dependency:

Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO)

Level

3

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

117

Page 117
Image 117
Siemens 440 manual P10173 Fixed frequency mode Bit, P10183 Fixed frequency mode Bit, P10193 Fixed frequency mode Bit, 117