Parameter Description

Issue 01/06

3.10Digital outputs

r0730

Number of digital outputs

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: COMMANDS

 

Max:

-

Displays number of digital outputs (relays).

Level

3

P0731[3] BI: Function of digital output 1

 

Min:

0:0

CStat:

CUT

Datatype: U32

Unit: -

Def:

52:3

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines source of digital output 1.

Level

2

DOUT channel

Invert DOUTs

 

0 ... 7

 

P0748 (0)

 

 

BI: Fct. of DOUT 1

 

 

Function

rxxxx.y

P0731.C

0

 

 

 

 

xxxx .y

(52:3)

1

-1

 

 

 

 

 

 

P0731 = xxxx.y

 

 

CO/BO: State DOUTs

int. 24 V

max. 100 mA

r0747

Kl.9

r0747.0

 

COM

Kl.20

NO Kl.19

or

NC Kl.18

Relay : max. load capability

Kl.28

DC 30 V / 5 A

AC 250 V / 2 A max. opening / closing time

5 / 10 ms

Index:

 

 

 

 

P0731[0] : 1st. Command data set (CDS)

 

 

P0731[1] : 2nd. Command data set (CDS)

 

 

P0731[2] : 3rd. Command data set (CDS)

 

 

Common Settings:

 

 

 

52.0

Drive ready

 

0

Closed

52.1

Drive ready to run

0

Closed

52.2

Drive running

 

0

Closed

52.3

Drive fault active

0

Closed

52.4

OFF2 active

 

1

Closed

52.5

OFF3 active

 

1

Closed

52.6

Switch on inhibit active

0

Closed

52.7

Drive warning active

0

Closed

52.8

Deviation setpoint/actual value

1

Closed

52.9

PZD control (Process Data Control)

0

Closed

52.A

Maximum frequency reached

0

Closed

52.B

Warning: Motor current limit

1

Closed

52.C

Motor holding brake (MHB) active

0

Closed

52.D

Motor overload

 

1

Closed

52.E

Motor running direction right

0

Closed

52.F

Inverter overload

1

Closed

53.0

DC brake active

 

0

Closed

53.1

Act. freq. f_act

> P2167 (f_off)

0

Closed

53.2

Act. freq. f_act

<= P1080 (f_min)

0

Closed

53.3

Act. current r0027 > P2170

0

Closed

53.4

Act. freq. f_act

> P2155 (f_1)

0

Closed

53.5

Act. freq. f_act

<= P2155 (f_1)

0

Closed

53.6

Act. freq. f_act

>= setpoint

0

Closed

53.7

Act. Vdc r0026 < P2172

0

Closed

53.8

Act. Vdc r0026 > P2172

0

Closed

53.A

PID output r2294 == P2292 (PID_min)

0

Closed

53.B

PID output r2294 == P2291 (PID_max)

0

Closed

Details:

 

Display functions

==> see parameter r0052, r0053

Motor holding brake

==> see parameter P1215

DC brake

==> see parameter P1232, P1233

84

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 84
Image 84
Siemens 440 manual Digital outputs, R0730 Number of digital outputs, P07313 BI Function of digital output