Issue 01/06

Parameter Description

3 Parameter Description

Note

Level 4 Parameters are not visible with BOP or AOP.

3.1Common parameters

r0000

Drive display

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: ALWAYS

 

Max:

-

Level

1

Displays the user selected output as defined in P0005.

Note:

Pressing the "Fn" button for 2 seconds allows the user to view the values of DC link voltage, output frequency, output voltage, output current, and chosen r0000 setting (defined in P0005).

r0002

Drive state

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: COMMANDS

 

Max:

-

Level

2

Displays actual drive state.

Possible Settings:

0Commissioning mode (P0010 != 0)

1Drive ready

2Drive fault active

3Drive starting (DC-link precharging)

4Drive running

5Stopping (ramping down)

Dependency:

State 3 visible only while precharging DC link, and when externally powered communications board is fitted.

P0003

User access level

 

 

Min:

0

 

CStat:

CUT

Datatype: U16

Unit: -

Def:

1

 

P-Group:

ALWAYS

Active: first confirm

QuickComm.: No

Max:

4

Level

1

Defines user access level to parameter sets. The default setting (standard) is sufficient for most simple applications.

Possible Settings:

0User defined parameter list - see P0013 for details on use

1Standard: Allows access into most frequently used parameters.

2Extended: Allows extended access e.g. to inverter I/O functions.

3Expert: For expert use only.

4Service: Only for use by authorized service personal - password protected.

P0004

Parameter filter

 

 

Min:

0

 

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

ALWAYS

Active: first confirm

QuickComm.: No

Max:

22

Filters available parameters according to functionality to enable a more focussed approach to commissioning.

Possible Settings:

0 All parameters

2Inverter

3Motor

4Speed sensor

5Technol. application / units

7Commands, binary I/O

8ADC and DAC

10Setpoint channel / RFG

12Drive features

13Motor control

20Communication

21Alarms / warnings / monitoring

22Technology controller (e.g. PID)

Example:

P0004 = 22 specifies that only PID parameters will be visible.

Level

1

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

25

Page 25
Image 25
Siemens 440 Common parameters, R0000 Drive display, R0002 Drive state, P0003 User access level, P0004 Parameter filter