Issue 01/06Faults and Alarms

F0015 No motor temperature signal

STOP II

Quit

Refer to F0001

Cause

-motor temperature sensor either short-circuited or open-circuit.

-if it is identified that a signal has been lost, then the temperature monitoring changes-over to monitoring based on the thermal-motor model.

F0020 Line supply phase missing

STOP II

Quit

Refer to F0001

Cause

-a fault is output if one of the three input phases is missing, the pulses are enabled and a load is present

Diagnosis & Remedy

Please check the following:

-are the power connections ok ?

F0021 Ground fault

STOP II

Quit

Refer to F0001

Cause

-the fault occurs if the sum of the phase currents is greater than 5 % of the inverter rated current.

NOTE

-this fault only occurs for inverters with 3 current sensors (sizes D to F, GX, FX).

Diagnosis & Remedy

Please check the following:

-are the connections at the motor terminal boxes o.k. ?

-are the motor cable connections at the inverter o.k. ?

F0022 Hardware monitoring active

STOP II

Quit

Refer to F0001

Cause

This fault (r0947 = 22 and r0949 = 1) occurs under the following circumstances:

(1)DC link overcurrent condition = IGBT short-circuit

(2)Braking chopper short-circuit

(3)Ground fault

(4)I/O module not correctly inserted

For the following sizes the above faults can occur:

-size A to C (1),(2),(3),(4)

-

size D to E (1),(2), (4)

-

size F

(1),(2)

The following faults only occur in conjunction with sizes FX / GX:

-UCE faults are identified if r0947 = 22 and the fault value r0949 = 12 or 13 or 14.

-I2C bus error is identified if r0947 = 22 and the fault value r0949 = 21 (power-down and then power-up again).

NOTE

All of these faults are assigned to a signal in the power module. This means that it is not possible to determine which fault actually occurred.

Diagnosis & Remedy

You must first identify as to whether the fault is permanent (i.e. the inverter cannot be started without the fault occurring) or it sporadically occurs (occasionally occurs or under certain operating conditions). Permanent fault F0022:

-check whether the I/O module is correctly inserted (refer to the Operating Instructions).

-is there a ground fault or short-circuit at the inverter output or at an IGBT? You can identify this by disconnecting the motor cable.

In the case that the fault occurs, if all of the external cables (with the exception from the line supply voltage) are disconnected, then with a high degree of probability, the drive unit is defective and must be repaired.

Sporadic fault F0022:

-this fault should be treated as "overcurrent". If fault F0022 sporadically occurs, the causes can be as follows:

-sudden load changes or mechanical obstructions

-extremely short ramp-up times (accelerating times)

-poor optimization of the sensorless closed-loop vector control

-incorrect braking resistor is installed with an excessively low resistance

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

309

Page 309
Image 309
Siemens 440 manual F0015 No motor temperature signal, F0020 Line supply phase missing, F0021 Ground fault, 309