Parameter Description

Issue 01/06

P2014[2] USS telegram off time

 

 

Min:

0

CStat:

CT

Datatype: U16

Unit: ms

Def:

0

P-Group:

COMM

Active: Immediately

QuickComm.: No

Max:

65535

Defines the telegram failure time for the serial interfaces with USS protocol.

Level

3

The telegram failure time defines the time within which a valid telegram must have been received. If a valid telegram is not received within the specified time, the drive inverter outputs fault F0070.

Index:

P2014[0] : Serial interface COM link

P2014[1] : Serial interface BOP link

Notice:

By default (time set to 0), no fault is generated (i.e. watchdog disabled).

r2015[8] CO: PZD from BOP link (USS)

 

Min:

-

Datatype: U16

Unit: -

Def:

-

P-Group: COMM

 

Max:

-

Level

3

Displays process data received via USS on BOP link (RS232 USS).

PZD4

PZD3

PZD2

PZD1

STW2

 

HSW

STW1

 

 

P2012

 

BCC

 

PZD

PKW

 

ADR

 

LGE

 

STX

 

Process data

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

USS telegram

r2015

 

 

[0]

r2032

 

[1]

 

 

[2]

 

.

[3]

 

 

 

.

 

r2033

.

[7]

 

 

STX

Start of text

 

LGE

Length

 

ADR

Address

 

PKW

Parameter ID value

PZD

Process data

 

BCC

Block check character

STW

Control word

 

HSW

Main setpoint

 

USS on BOP link PZD mapping to parameter r2015

Index:

r2015[0] : Received word 0

r2015[1] : Received word 1

r2015[2] : Received word 2

r2015[3] : Received word 3

r2015[4] : Received word 4

r2015[5] : Received word 5

r2015[6] : Received word 6

r2015[7] : Received word 7

Note:

The control words can be viewed as bit parameters r2032 and r2033.

Restrictions:

-If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be transferred in the 1st PZD-word.

-If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the 2nd PZD-word,

-When P2012 is greater than or equal to 4 the additional control word (2nd control word) must transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719).