Issue 01/06

Parameter Description

P0304[3] Rated motor voltage

 

 

Min:

10

CStat:

C

Datatype: U16

Unit: V

Def:

230

P-Group:

MOTOR

Active: first confirm

QuickComm.: Yes

Max:

2000

Level

1

Nominal motor voltage [V] from rating plate. Following diagram shows a typical rating plate with the locations of the relevant motor data.

Line supply voltage

1 AC 110 V *)

1 AC 230 V

3 AC 230 V

3 AC 400 V

3 AC 500 V

MICROMASTER 410

X

X

-

-

-

MICROMASTER 411

-

-

-

X

-

 

 

 

 

 

 

MICROMASTER 420

-

X

X

X

-

 

 

 

 

 

 

MICROMASTER 430

-

-

-

X

-

 

 

 

 

 

 

MICROMASTER 440

-

X

X

X

X

 

 

 

 

 

 

*) Line supply voltage 1-ph. 110 V AC is stepped-up --> frequency inverter output voltage 3-ph. 230 V AC

Index:

P0304[0] : 1st. Drive data set (DDS)

P0304[1] : 2nd. Drive data set (DDS)

P0304[2] : 3rd. Drive data set (DDS)

Dependency:

-Changeable only when P0010 = 1 (quick commissioning).

-Default value is depending on inverter type and its rating data.

Caution:

The input of rating plate data must correspond with the wiring of the motor (star / delta). This means, if delta wiring is used for the motor, delta rating plate data has to be entered.

IEC Motor

 

 

 

 

 

 

W2

U2

V2

W2

U2

V2

 

 

 

 

U1

V1

W1

U1

V1

W1

 

 

U1

 

U1

 

 

 

 

 

 

V1

 

V1

 

 

W1

 

W1

 

 

Delta connection

Star connection

e.g.: Volts 230 V (Delta connection) / 400 V (Star connection)

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

51

Page 51
Image 51
Siemens 440 manual P03043 Rated motor voltage, Active first confirm QuickComm. Yes Max 2000, IEC Motor