Issue 01/06

Parameter Description

P0724

Debounce time for digital inputs

 

Min:

0

 

CStat:

CT

Datatype: U16

Unit: -

Def:

3

 

P-Group:

COMMANDS

Active: Immediately

QuickComm.: No

Max:

3

Defines debounce time (filtering time) used for digital inputs.

Possible Settings:

0No debounce time

12.5 ms debounce time

28.2 ms debounce time

312.3 ms debounce time

Level

3

P0725

PNP / NPN digital inputs

 

Min:

0

 

CStat:

CT

Datatype: U16

Unit: -

Def:

1

 

P-Group:

COMMANDS

Active: Immediately

QuickComm.: No

Max:

1

Level

3

Switches between active high (PNP) and active low (NPN). This is valid for all digital inputs simultaneously.

The following is valid by using the internal supply:

Possible Settings:

0NPN mode ==> low active

1PNP mode ==> high active

Value:

NPN: Terminals 5/6/7/8/16/17 must be connected via terminal 28 ( O V).

PNP: Terminals 5/6/7/8/16/17 must be connected via terminal 9 (24 V).

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

83

Page 83
Image 83
Siemens 440 manual P0724 Debounce time for digital inputs, P0725 PNP / NPN digital inputs