Parameter Description

Issue 01/06

P1245[3] Switch on level kin. buffering

 

Min:

65

CStat:

CUT

Datatype: U16

Unit: %

Def:

76

P-Group:

FUNC

Active: Immediately

QuickComm.: No

Max:

115

Level

3

Enter switch-on level for kinetic buffering (KIB) in [%] relative to supply voltage (P0210).

P1245[V] = P1245[%] 2 P0210

100

Index:

P1245[0] : 1st. Drive data set (DDS)

P1245[1] : 2nd. Drive data set (DDS)

P1245[2] : 3rd. Drive data set (DDS)

Warning:

Increasing the value too much, may interfere with the drive normal operation.

Note:

Changing P1254 does not affect the switch-on-level for KIB.

r1246[3]

CO:Switch-on level kin buffering

 

Min:

-

 

Datatype: Float

Unit: V

Def:

-

 

P-Group: FUNC

 

Max:

-

Displays switch-on level of kinetic buffering (KIB, Vdc min controller).

Level

3

Depending on the setting selected, the frequency limit defined in P1245 is used to either hold the speed or disable pulses. If not enough regeneration is produced, drive may trip undervoltage.

P1247[3] Dyn. factor of kinetic buffering

 

Min:

10

CStat:

CUT

Datatype: U16

Unit: %

Def:

100

P-Group:

FUNC

Active: Immediately

QuickComm.: No

Max:

200

Enters dynamic factor for kinetic buffering (KIB, Vdc-min controller).

Level

3

P1247 = 100 %

means parameters P1250, P1251 and P1252 (gain, integration time and differential time) are used as set. Otherwise, these are multiplied by P1247 (dynamic factor of Vdc-min).

Index:

P1247[0] : 1st. Drive data set (DDS)

P1247[1] : 2nd. Drive data set (DDS)

P1247[2] : 3rd. Drive data set (DDS)

Note:

Vdc controller adjustment is calculated automatically from motor and inverter data.

P1250[3]

Gain of Vdc-controller

 

 

Min:

0.00

Level

 

CStat:

CUT

Datatype: Float

Unit: -

Def:

1.00

4

 

P-Group:

FUNC

Active: Immediately

QuickComm.: No

Max:

10.00

 

Index:

Enters gain for Vdc controller.

 

 

 

 

 

P1250[0]

: 1st. Drive data set (DDS)

 

 

 

 

 

 

 

 

 

 

P1250[1]

: 2nd. Drive data set (DDS)

 

 

 

 

 

P1250[2]

: 3rd. Drive data set (DDS)

 

 

 

 

P1251[3]

Integration time Vdc-controller

 

Min:

0.1

Level

 

CStat:

CUT

Datatype: Float

Unit: ms

Def:

40.0

4

 

 

 

P-Group:

FUNC

Active: Immediately

QuickComm.: No

Max:

1000.0

 

Enters integral time constant for Vdc controller.

Index:

P1251[0] : 1st. Drive data set (DDS)

P1251[1] : 2nd. Drive data set (DDS)

P1251[2] : 3rd. Drive data set (DDS)

P1252[3]

Differential time Vdc-controller

 

Min:

0.0

Level

 

CStat:

CUT

Datatype: Float

Unit: ms

Def:

1.0

4

 

 

 

P-Group:

FUNC

Active: Immediately

QuickComm.: No

Max:

1000.0

 

Enters differential time constant for Vdc controller.

Index:

P1252[0] : 1st. Drive data set (DDS)

P1252[1] : 2nd. Drive data set (DDS)

P1252[2] : 3rd. Drive data set (DDS)

150

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 150
Image 150
Siemens 440 P12453 Switch on level kin. buffering, R12463 COSwitch-on level kin buffering, P12503 Gain of Vdc-controller