Siemens 440 manual P0010 Commissioning parameter, P0011 Lock for user defined parameter

Models: 440

1 328
Download 328 pages 28.01 Kb
Page 27
Image 27

Issue 01/06

Parameter Description

P0010

Commissioning parameter

 

Min:

0

 

CStat:

CT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

ALWAYS

Active: first confirm

QuickComm.: No

Max:

30

Level

1

Filters parameters so that only those related to a particular functional group are selected.

Possible Settings:

0Ready

1Quick commissioning

2Inverter

29Download

30Factory setting

Dependency:

- Reset to 0 for inverter to run.

- P0003 (user access level) also determines access to parameters.

Note:

P0010 = 1

The inverter can be commissioned very quickly and easily by setting P0010 = 1. After that only the important parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be entered one after the other. The end of quick commissioning and the start of internal calculation will be done by setting P3900 = 1 - 3. Afterward parameter P0010 and P3900 will be reset to zero automatically.

P0010 = 2

For service purposes only.

P0010 = 29

To transfer a parameter file via PC tool (e.g.: DriveMonitor, STARTER) parameter P0010 will be set to 29 by the PC tool. When download has been finished PC tool resets parameter P0010 to zero.

P0010 = 30

When resetting the parameters of inverter P0010 must be set to 30. Resetting of the parameters will be started by setting parameter P0970 = 1. The inverter will automatically reset all its parameters to their default settings. This can prove beneficial if you experience problems during parameter setup and wish to start again. Duration of factory setting will take about 60 s.

P0011

Lock for user defined parameter

 

Min:

0

 

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

FUNC

Active: first confirm

QuickComm.: No

Max:

65535

Details:

See parameter P0013 (user defined parameter)

Level

3

P0012

Key for user defined parameter

 

Min:

0

 

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

FUNC

Active: first confirm

QuickComm.: No

Max:

65535

Level

3

Details:

See parameter P0013 (user defined parameter).

P0013[20] User defined parameter

 

 

Min:

0

Level

 

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

3

 

 

 

P-Group:

FUNC

Active: first confirm

QuickComm.: No

Max:

65535

 

Defines a limited set of parameters to which the end user will have access.

Instructions for use:

1.Set P0003 = 3 (expert user)

2.Go to P0013 indices 0 to 16 (user list)

3.Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list. The following values are fixed and cannot be changed:

-P0013 index 19 = 12 (key for user defined parameter)

-P0013 index 18 = 10 (commissioning parameter filter)

-P0013 index 17 = 3 (user access level)

4.Set P0003 = 0 to activate the user defined parameter.

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

27

Page 27
Image 27
Siemens 440 P0010 Commissioning parameter, P0011 Lock for user defined parameter, P0012 Key for user defined parameter