Parameter Description

Issue 01/06

P0845[3] BI: 2. OFF2

 

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

19:1

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Level

3

Defines second source of OFF2.

The first three digits describe the parameter number of the command source and the last digit denotes the bit setting for that parameter. If one of the digital inputs is selected for OFF2, the inverter will not run unless the digital input is active.

Index:

P0845[0] : 1st. Command data set (CDS)

P0845[1] : 2nd. Command data set (CDS)

P0845[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

19.0= ON/OFF1 via BOP

Details:

See parameter P0844.

P0848[3] BI: 1. OFF3

 

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

1:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Level

3

Defines first source of OFF3.

The first three digits describe the parameter number of the command source and the last digit denotes the bit setting for that parameter. If one of the digital inputs is selected for OFF3, the inverter will not run unless the digital input is active.

 

OFF3

 

t

 

 

f

 

 

 

 

 

 

 

 

 

f max

 

 

f act,motor

 

(P1082)

 

 

 

 

 

f 2

 

P2168

 

 

 

 

 

f

act,inverter

 

 

 

 

 

P2167

 

 

 

 

 

0

P2168

 

t

 

 

 

 

tdown,OFF3 =

P1135

f 2

 

tdown,OFF3

 

P1082

 

 

 

 

 

r0052 Bit02

P1135

 

 

 

 

 

 

 

 

 

Operation

Pulse cancellation

t

Index:

P0848[0] : 1st. Command data set (CDS)

P0848[1] : 2nd. Command data set (CDS)

P0848[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

19.0= ON/OFF1 via BOP

Dependency:

Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).

Note:

- OFF3 means fast ramp-down to 0 Hz through P1135. - OFF3 is low-active.

- Priority of all OFF commands: OFF2, OFF3, OFF1

104

MICROMASTER 440 Parameter List