Parameter Description

Issue 01/06

P2040

CB telegram off time

 

 

Min:

0

 

CStat:

CT

Datatype: U16

Unit: ms

Def:

20

 

P-Group:

COMM

Active: Immediately

QuickComm.: No

Max:

65535

Defines time after which a fault will be generated (F0070) if no telegram is received via the link.

Level

3

The telegramm off time defines the time, within which a valid telegram must be received. If no valid telegram is received within that time, the inverter trips with F0070.

Dependency:

Setting 0 = watchdog disabled

P2041[5] CB parameter

 

 

Min:

0

CStat:

CT

Datatype: U16

Unit: -

Def:

0

P-Group:

COMM

Active: first confirm

QuickComm.: No

Max:

65535

Configures a communication board (CB).

Index:

P2041[0] : CB parameter 0

P2041[1] : CB parameter 1

P2041[2] : CB parameter 2

P2041[3] : CB parameter 3

P2041[4] : CB parameter 4

Details:

See relevant communication board manual for protocol definition and appropriate settings.

Level

3

r2050[8] CO: PZD from CB

 

Min:

-

Datatype: U16

Unit: -

Def:

-

P-Group: COMM

 

Max:

-

Displays PZD received from communication board (CB).

Level

3

 

 

 

 

r2050

 

 

 

 

 

[0]

r2090

 

 

 

 

[1]

 

 

 

 

 

[2]

 

 

 

 

 

[3]

 

 

 

 

 

.

 

 

 

 

 

.

r2091

PZD4

PZD3

PZD2

PZD1

.

[7]

 

STW2

 

HSW

STW1

 

CB-Frame

PZD

PKW

Process data

Parameter

P2041[0] CB telegram

CB-Frame

PKW Parameter ID value PZD Process data

STW Control word HSW Main setpoint

CB on COM link PZD mapping to parameter 2050r

Index:

r2050[0] : Received word 0

r2050[1] : Received word 1

r2050[2] : Received word 2

r2050[3] : Received word 3

r2050[4] : Received word 4

r2050[5] : Received word 5

r2050[6] : Received word 6

r2050[7] : Received word 7

Note:

The control words can be viewed as bit parameters r2090 and r2091.

Restrictions:

-If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be transferred in the 1st PZD-word.

-If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the 2nd PZD-word,

-When P2012 is greater than or equal to 4 the additional control word (2nd control word) must transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719).