Issue 01/06

Parameter Description

Caution:

Parameter P2000 represents the reference frequency of the above mentioned interfaces. A maximum frequency setpoint of 2*P2000 can be applied via the corresponding interface. Unlike parameter P1082 (Max. Frequency) this limits the inverter frequency internally independent of the reference frequency. By modification of P2000 it will also adapt the parameter to the new settings.

 

f (Hex)

 

PZD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setpoint

 

 

 

 

 

 

 

 

channel

 

f (%)

 

 

 

 

f [Hz]

 

 

 

 

 

 

ADC

 

Normalization

 

 

 

 

 

 

 

 

 

 

f[Hz] =

f(Hex)

P2000 =

f(%)

P2000

4000(Hex)

100 %

 

 

 

 

P1082

 

 

 

 

 

 

 

 

Motor

f_act

 

f_act,limit

control

 

 

Limitation

f_act,limit = min(P1082, f_act)

Notice:

Reference variables are intended as an aid to presenting setpoint and actual value signals in a uniform manner. This also applies to fixed settings entered as a precentage. A value of 100 % (USS / CB) corresponds to a process data value of 4000H, or 4000 0000H in the case of double values.

In this respect, the following parameters are available:

 

P2000

Reference frequency

Hz

 

 

 

P2001

Reference voltage

V

 

 

 

P2002

Reference current

A

 

 

 

P2003

Reference torque

Nm

 

 

 

P2004

Reference power

kW

 

 

f(P0100)

 

hp

 

 

 

 

 

 

 

 

 

 

 

 

 

P2001[3] Reference voltage

 

 

Min:

10

Level

 

CStat:

CT

Datatype: U16

Unit: V

Def:

1000

3

 

 

 

P-Group:

COMM

Active: first confirm

QuickComm.: No

Max:

2000

 

Full-scale output voltage (i.e. 100 % ) used over serial link (corresponds to 4000H).

Index:

P2001[0] : 1st. Drive data set (DDS)

P2001[1] : 2nd. Drive data set (DDS)

P2001[2] : 3rd. Drive data set (DDS)

Example:

P2001 = 230 specifies that 4000H received via USS denotes 230 V.

If a BICO connection is made between two parameters, the "unit" of the parameters (standardized (Hex) or physical (i.e. V) values) may differ. MICROMASTER implicitly makes an automatic conversion to the target value.

r0026 P0771

DAC

y[Hex]= P2001[V]r0026[V]4000[Hex]

x[V]y[Hex]

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

193

Page 193
Image 193
Siemens 440 manual P20013 Reference voltage, 193, Normalization, Limitation