Parameter Description

 

 

 

 

Issue 01/06

 

 

 

 

 

 

P0706[3] Function of digital input 6

 

Min:

0

 

Level

 

CStat:

CT

Datatype: U16

Unit: -

Def:

15

 

2

 

 

 

 

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

99

 

 

Selects function of digital input 6.

Possible Settings:

0

Digital input disabled

1

ON/OFF1

2

ON reverse /OFF1

3

OFF2

- coast to standstill

4

OFF3

- quick ramp-down

9

Fault acknowledge

10

JOG right

11

JOG left

 

12

Reverse

13

MOP up

(increase frequency)

14

MOP down (decrease frequency)

15

Fixed setpoint (Direct selection)

16

Fixed setpoint (Direct selection + ON)

25

DC brake enable

29

External trip

33

Disable additional freq setpoint

99

Enable BICO parameterization

Index:

 

 

P0706[0] : 1st. Command data set (CDS)

P0706[1] : 2nd. Command data set (CDS)

P0706[2] : 3rd. Command data set (CDS)

Details:

 

 

See P0701 (function of digital input 1).

P0707[3] Function of digital input 7

 

Min:

0

Level

 

CStat:

CT

Datatype: U16

Unit: -

Def:

0

2

 

 

 

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

99

 

Selects function of digital input 7 (via analog input).

Possible Settings:

0Digital input disabled

1ON/OFF1

2ON reverse /OFF1

3

OFF2 - coast to standstill

4OFF3 - quick ramp-down

9Fault acknowledge

10JOG right

11JOG left

12Reverse

13MOP up (increase frequency)

14MOP down (decrease frequency)

25DC brake enable

29External trip

33Disable additional freq setpoint

99Enable BICO parameterization

Index:

P0707[0] : 1st. Command data set (CDS)

P0707[1] : 2nd. Command data set (CDS)

P0707[2] : 3rd. Command data set (CDS)

Note:

Signals above 4 V are active, signals below 1,6 V are inactive.

Details:

See P0701 (function of digital input 1).

80

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 80
Image 80
Siemens 440 manual P07063 Function of digital input, P07073 Function of digital input